New KSEP 8.0 software
- Automatic preparation and test run
- New control variables for quality control
- Extended data export options
- Support also for the 1m3 container
- Built-in calibration
2016 – 2024 manufactured by TÜV SÜD Schweiz AG, Basel, Switzerland, under licence from Cesana AG, Bettingen, Switzerland
From 2025 manufactured by REMBE® Research+Technology Center GmbH, Brilon, Germany, under licence from Cesana AG, Bettingen, Switzerland
Knowledge of the following explosion characteristics is essential for the dimensioning of protective measures. These parameters are determined in accordance with international standards in the 20 L laboratory apparatus:
Over the almost 5 decades, the instrumentation has always been adapted to the state of the art. The aim has always been full backwards compatibility. Equipment from 1976 onwards can be brought up to date.
Absolute pressure measurement
Instead of the analogue and relative pressure display for the sphere and pre-chamber, absolute and digital measurements are now used. Errors caused by the barometric ambient pressure are eliminated.
Limiting oxygen concentration (LOC)
Thanks to the precise and absolute pressure measurement in the sphere and pre-chamber, it is possible to produce the desired air/inert gas mixture using the partial pressure method. Only one inert gas cylinder is required for this. The gas mixtures are created fully automatically. In contrast to the previous partial pressure method, the same mixture is now prepared in the pre-chamber and sphere.